Ventilation Systems Coupled with Forced Air Heating Systems

(1)  This Article applies to a mechanical ventilation system serving a house or an individual dwelling unit that contains a forced air heating system which is used for delivery of ventilation air.

(2)  Where a mechanical ventilation system serves a Type I dwelling unit, a ventilation supply inlet is not required.

(3)  Where a mechanical ventilation system serves a Type II dwelling unit, the system shall include a heat recovery ventilator, coupled to the forced air heating system, installed in accordance with Article 9.32.3.11.

(4)  The forced air heating system circulation fan shall be controlled by a manual switch located adjacent to the ventilation fan switch required in Sentence 9.32.3.4.(4).

(5)  The switch required in Sentence (4) shall be identified by the words CIRCULATION FAN.