Support of Walls

Support of Walls (1)  Non-loadbearing walls parallel to the floor joists shall be supported by joists beneath the wall or on blocking between the joists.     (2)  Blocking referred to in Sentence (1) for the support of non-loadbearing walls shall be not less than 38 mm by 89 mm lumber, spaced not more than 1.2 m apart. […]
Read more

Table – Size and Spacing of Furring

Table – Size and Spacing of Furring Table 9.29.3.1. Forming Part of Sentence 9.29.3.1.(1) Table 9.29.3.1. Ontario Regulation 332/12 Building Code,   Information published by oncodes.ca for educational purposes only.
Read more

Taping Low Temperature Conditions

Taping Low Temperature Conditions (1)  In cold weather, heat shall be provided to maintain a temperature of not below 10°C for 48 h prior to taping and finishing and maintained for not less than 48 h after that. Article 9.29.5.10 Ontario Regulation 332/12 Building Code,   Information published by oncodes.ca for educational purposes only. Drywall mudding […]
Read more

Top Plates

Top Plates (1)  Top plates in walls shall not be notched, drilled or otherwise weakened to reduce the undamaged width to less than 50 mm unless the weakened plates are suitably reinforced. Article 9.23.5.4. Ontario Regulation 332/12 Building Code,   Information published by oncodes.ca for educational purposes only.
Read more

Top Plates

Top Plates (1)  Except as permitted in Sentences (2) to (4), no fewer than two top plates shall be provided in loadbearing walls.     (2)  A single top plate is permitted to be used in a section of a loadbearing wall containing a lintel provided the top plate forms a tie across the lintel.     (3)  A single […]
Read more

Vapour Barrier Materials

Vapour Barrier Materials (1)  Vapour barriers shall have a permeance not greater than 60 ng/(Pa∙s∙m2), measured in accordance with ASTM E96 / E96M, “Water Vapor Transmission of Materials”, using the desiccant method (dry cup).     (2)  Where the intended use of the interior space will result in high moisture generation, the assembly shall be designed according to […]
Read more

Wall Stud Size and Spacing

Wall Stud Size and Spacing (1)  Except as provided in Sentence (2), the size and spacing of studs shall conform to Table 9.23.10.1. (2)  Studs for walls not listed in Table 9.23.10.1. and supporting roof loads shall conform to Tables A-30 to A-33, provided,     (a)   the studs are clad with not less than 9.5 mm thick […]
Read more