Joints to be Offset or Reinforced
(1) Vertical joints in adjacent masonry courses shall be offset unless each wythe of masonry is reinforced with the equivalent of no fewer than two corrosion-resistant steel bars of 3.76 mm diam placed in the horizontal joints at vertical intervals not exceeding 460 mm.
(2) Where joints in the reinforcing referred to in Sentence (1) occur, the bars shall be lapped not less than 150 mm.
=
Article 9.20.9.1 Ontario Regulation 332/12 Building Code, O. Reg. 332/12: BUILDING CODE (ontario.ca) © Queen’s Printer for Ontario, 2021