Indirect Connections

(1)  Where a fixture or device is indirectly connected, the connections shall be made by terminating the fixture drain above the flood level rim of a directly connected fixture to form an air break.

(2)  The size of the air break shall be at least 25 mm.

=

Article 7.3.3.11. Ontario Regulation 332/12 Building Code, Information published by oncodes.ca for educational purposes only